Technical data                      

General Specifications
Sensing distance 30…400mm
Adjustment range 50…400mm
Unusable area 0…30mm
Standard target plate 100mm×100mm
Transducer frequency About 310kHz
Response delay About 50ms
Indicators/Operating means
LED blue Power on
LED yellow indication of the switching state
Flashing:program function object detected
LED red permanently red: Error Red,flashing:program
function,object not detected
Electrical specifications
Operating voltage U B 10…30VDC,ripple10%ss
No-load supply current ≤30mA
Input
Input type 1 TEACH-IN input Operating distance
A1:-U B …+1V,operating distanceA2:+6…
+ U B  Input impedance:>4.7KΩ
TEACH-IN programmable pulse :≥1S
Output
Output type 1 switch output E5,PNP NO/NC,programmable
Rated operational current 100mA,short-circuit/overload protected
Default setting Switching point A1:70mm Switching point A2: 800mm
Voltage drop ≤ 3V
Repeat accuracy ≤ 1%
Switching frequency f ≤ 8 HZ
Range hysteresis H 1% of the set operating distance
Temperature influence ± 1.5% of full-scale value
Ambient conditions
Ambient temperature -25…70℃(248...343K)
Storage temperature -40…85℃(233...358K)
Mechanical specifications
Protection grade IP67
Connection V1 connector(M12×1),4-pin
Material Housing brass,nickel-plated
Transducer epoxy resin/hollow glass sphere mixture;
Polyurethane foam
Weight 25g

Dimension                          

Adjusting the switching points        

The ultrasonic sensor features a switch output with two teachable switching points. These are set by applying the supply voltage - U B or + U B to the TEACH-IN input. The supply voltage must be applied to the TEACH-IN input for at least 1s.LEDs indicate whether the sensor has recognised the target during the TEACH-IN procedure. Switching point A1 is taught with - U B ,A2 with +U B. Five different output functions can be set.
1.  Window mode, normally-open function.
2.  Window mode, normally-closed function.
3.  One switching point,normally-open function
4. One switching point,normally-closed function.
5.  Detection of objet presence.
Switching point, Setting distance only after power on. The internal clock can assure can't be changed after 5 mins when power
on. If want to change the switching point, the user can only setting the request distance after power restart.